8.- PREVENTIVE MAINTENANCE SUMMARY CHART
OPERATIONS TO BE CARRIED OUT
BLOWDOWN
GRID
BASIN
WATER MAKE-UP
ELECTRIC PUMP
WATER
DISTRIBUTION
DRIFT ELIMINATOR
MOTOR
FAN
CASING
COLD WEATHER
OPERATION
INSPECTION FOR FOULING
M M M
INSPECTION OF THE GENERAL CONDITION
M M/N M M M S N
CLEANING AND DISINFECTION
M M M/N M/N S/N S S S
BASIN WATER LEVEL
M
INSPECTION FOR OVERHEATING, NOISE AND VIBRATION
M M
INSPECTION FOR LEAKS
S/N S/N S/N
TIGHTENING OF BOLTS AND ANCHORING
N N
BALANCING AND ALIGNMENT
LUBRICATION (please check also the instruction manual of the suppliers)
N N
BLOWDOWN FLOW AND CONCENTRATION CYCLE CHECKING
D
D = Every Day
M = Every Month
S = Every six Months
N = When Needed