A-38
Specifications/Product Ordering
Thermostats & Hygrostats
Operating Voltage ........................................................24…120, 277 Vac
Frequency ..............................................................................50 or 60 Hz
Set Point Adjustment Range ............................. 50 to 85°F (10 to 29°C)
Switching Differential ........................................................ < 1.8°F (1°C)
Switch Rating ................................................. 6A RES, 2A FLA, 12A LRA
Time Constant ...............................................................................14 min.
Switch Action Output ..................................SPDT Two-position (On/Off)
Operation–Conditions
Operating Temperature .................................... 32 to 122°F (0 to 50°C)
Relative Humidity ................................................................... <95% RH
Transportation/Storage Conditions
Temperature ...............................................-4 to +122°F (-20 to +50°C)
Relative Humidity ................................................................... <95% RH
Housing
Material .......................................................................................Plastic
Color ............................................................................................ White
Bellows ..................................................... Environmentally-friendly gas
Wiring ........................................................... Screw terminals for wires of
2 x 16 AWG or 1 x 14 AWG, 20 AWG max.
Agency Listings ........................................Conforms to CE requirements
UL listed to 873
cUL listed to Canadian standard C22.2 No. 24-93
Shipping Weight ........................................................... 0.31 lb. (0.14 kg)
Table Note
1. Includes wall plate, ARG70, to be UL compliant for switching line voltage.
Electric Dry
Description Wall Box
1
Wall
Thermostat for heating or cooling only RAA10CW RAA10C
with concealed set point knob
Thermostat for heating or cooling only RAA20UW RAA20U
with exposed set set point knob
Thermostat for heating or cooling only RAA30UW RAA30U
with exposed set point knob and On/Off switch
Thermostat for heating/cooling RAA40UW RAA40U
with exposed set point knob and Heat/Cool/Off selector switch
Part Nos.
RAA…
Page
75
Page
75